From AFFF to SFFF: Considerations for Modernizing Foam Systems

Modernizing foam suppression systems is no longer just a “fire protection upgrade.” For many facilities, it has become a cross-functional program that touches safety, environmental responsibility, compliance, and operational continuity. As organizations evaluate a transition from legacy AFFF-based protection toward newer fluorine-free options (often described as SFFF or “F3”), the most successful projects start with clear terminology, realistic performance expectations, and a plan for engineering, cleaning, testing, and training.

This guide walks through the practical considerations for converting fixed foam systems—while also addressing how AR-AFFF Foam and tools like an AR-AFFF Fire Extinguisher may still fit into interim risk controls during a phased modernization.

Key Terms to Align Your Team

Before comparing products or requesting quotes, get everyone using the same language:

  • AFFF: Aqueous film-forming foam historically used for Class B hydrocarbon fuel fires.

  • AR-AFFF Foam: Alcohol-resistant AFFF designed for both hydrocarbon fuels and polar solvents (e.g., alcohols, ketones) where standard AFFF can be quickly destroyed.

  • SFFF / F3: “Synthetic fluorine-free foam” families designed without intentionally added fluorosurfactants. Performance relies on stable bubbles, cooling, and vapor suppression rather than a fluorinated film.

  • AR-SFFF: Alcohol-resistant fluorine-free options intended for polar solvent exposure, when available and listed for the hazard.

  • Listing / Approval: A formal performance validation under specific test protocols and configurations. In real projects, the “system as installed” (concentrate + proportioning + discharge devices + hydraulics) must align with the listed design.

The Reality Check: “Drop-In Replacement” Is Rare

One of the most common conversion mistakes is treating a foam transition like a simple chemical swap. In practice, many systems are engineered and validated around:

  • Required application density (flow per area)

  • Foam quality and expansion (how the foam is generated)

  • Discharge device type (aspirating vs non-aspirating)

  • Hydraulic constraints (pressure, pipe sizing, friction losses)

  • Compatibility across valves, proportioners, and storage vessels

That means a “concentrate-only” change can unintentionally reduce performance—or create a system that no longer matches its original basis of design. Successful modernization starts with an engineering review that treats the conversion as a system-level change.

Performance and Design Differences That Change Your Hardware

Film vs Barrier: Why Technique and Application Matter

Legacy AFFF performance is often associated with film-forming behavior. Fluorine-free alternatives generally depend more on bubble blanket integrity, cooling, and vapor suppression. That difference can affect:

  • Knockdown time (how quickly flames are controlled)

  • Burnback resistance (how well the blanket resists re-ignition)

  • Required discharge approach (gentle application can matter more to avoid foam blanket disruption)

Density, Flow, and Water Supply Impacts

In many conversion scenarios, meeting performance targets with fluorine-free foams can require increased application rates, adjusted device selection, or both. If the new design calls for higher flow, it can cascade into:

  • Higher demand on fire pumps and water supply

  • Larger proportioning equipment capacity

  • Potential pipe upsizing to manage friction loss

  • Changed discharge pressures at the most remote outlets

  • Recalculated concentrate quantity and storage volume

Foam Quality and Discharge Devices

The same foam concentrate can behave differently depending on how it is aerated and discharged. During modernization, evaluate whether your existing discharge devices were chosen for a film-forming approach and whether they can deliver the foam quality required for your selected fluorine-free option.

Start With Hazard Review: Choose Foam Based on What You Actually Protect

Foam selection should never begin with “what do other sites use?” It should begin with a hazard map:

  • Fuel type: Hydrocarbon fuels vs polar solvents (and whether both can occur in the same area)

  • Storage and process conditions: Tank type, bunding, drainage, spill geometry, and likely fire sizes

  • Facility layout: Obstructions, elevation changes, and access constraints

  • Environment: Wind exposure, temperature extremes, and corrosive atmospheres

  • Operational realities: Who responds, how quickly, and what training level

If polar solvents are credible, alcohol resistance is typically non-negotiable. That’s where AR-AFFF Foam has historically been selected—and where modern equivalents must be carefully validated for the specific scenario.

Modernization Scope: What May Need to Change (and Why)

Proportioning and Pumping Systems

Your proportioning system must accurately mix concentrate at the required percentage across the full operating range. During conversion, confirm:

  • Compatibility between the selected concentrate and proportioner type

  • Viscosity and temperature range impacts on accuracy

  • Ability to maintain proportioning at low and high flows

  • Calibration and test methods available for verification

Concentrate Storage Tanks and Materials Compatibility

Modernization often includes a review of storage vessels (bladder tanks, atmospheric tanks, totes) and the materials in contact with the foam. Confirm chemical compatibility with seals, gaskets, and linings—especially if your site has a history of long-term storage or infrequent turnover.

Discharge Devices: Nozzles, Sprinklers, Foam Makers

Device selection is one of the most important decisions in a conversion. Devices strongly influence foam quality, distribution, and the ability to maintain a stable blanket. In some cases, modernization requires replacing or re-orificing outlets to meet the new design density and pressure requirements.

Detection and Control Logic

If your legacy system has nuisance alarms or a history of false discharge risk, modernization is an opportunity to improve reliability. Consider whether updated detection, zoning, and release logic can reduce accidental discharges while still meeting response time needs.

Corrosion and Harsh Environments

Facilities near saltwater, in chemical processing environments, or with high humidity may benefit from upgraded materials selection. Modernization is a chance to standardize on corrosion-resistant components where lifecycle costs justify the change.

Contamination, Cleaning, and Disposal: The Work Nobody Can Skip

Transitioning away from AFFF frequently includes managing PFAS-related concerns. Even if your new foam concentrate is fluorine-free, residual material can remain in:

  • Concentrate tanks and bladder tanks

  • Proportioners and concentrate manifolds

  • Concentrate piping, valves, check valves, and strainers

  • Discharge devices and low-point drains

Plan for Residuals and Rebound Risk

Cleaning expectations should be defined up front. Some components may be flushable; others may be more practical to replace depending on accessibility, cost, and contamination risk tolerance.

Wastewater Management Is Part of the Project

Flushing and testing can generate contaminated liquids that require controlled collection and disposal. Build a plan that includes:

  • Containment (berms, drain isolation, temporary tanks)

  • Sampling strategy (where and when to sample)

  • Approved handling and disposal routes

  • Documentation for compliance and internal reporting

Testing and Commissioning: Proving the New System Works

Commissioning should be treated as a staged verification process—not a single event. A practical approach often looks like this:

  1. Engineering validation: confirm hydraulics, densities, and device selection match the design basis.

  2. Water-only functional testing: verify valve operations, alarms, detection logic, and flow paths.

  3. Proportioning verification: confirm mixing accuracy using accepted field methods.

  4. Foam quality confirmation: verify that the discharged foam meets expected quality for the selected devices.

  5. Documentation and handover: produce test records, as-builts, maintenance plans, and training materials.

When discharge testing creates disposal complexity, many sites use controlled, minimized testing strategies—while still maintaining confidence that the system will perform as intended for the specific hazard.

Training and Maintenance After the Conversion

Modernization is only successful if responders and maintenance teams can operate the new system under stress.

Update Response Tactics

Because fluorine-free performance can be more sensitive to application method, training should include:

  • How to apply foam without breaking the blanket

  • Understanding the difference between “knockdown” and “securement”

  • Re-application triggers and burnback awareness

  • Coordination between fixed systems and manual firefighting streams

Storage and Routine Checks

Review storage and turnover practices for concentrate. Maintain clear records for:

  • Batch identification and shelf-life guidance

  • Sampling schedules

  • Compatibility controls (avoiding mixing products unintentionally)

  • Preventive maintenance for proportioners and valves

Partnering and Program Management: How to Avoid Costly Missteps

Foam modernization typically spans multiple disciplines: fire protection engineering, EHS, operations, procurement, waste management, and sometimes legal/compliance stakeholders. A strong conversion plan includes:

  • A site-specific hazard and system assessment

  • Clear performance targets and acceptance criteria

  • A contamination and disposal plan with logistics and vendors identified

  • Commissioning steps that balance validation needs and waste constraints

  • Training and maintenance updates for long-term readiness

When selecting a partner or contractor, prioritize proven capability in system assessment, change-out execution, and commissioning documentation—not just concentrate supply.

Bridging Strategy: Managing AR-AFFF Foam During Transition

Many facilities cannot modernize every area at once. During a phased program, you may temporarily operate with legacy AR-AFFF Foam in some systems while converting others. If so, treat “mixed environment” operations as a major safety risk to control.

Practical Controls to Reduce Transition Risk

  • Labeling and segregation: clearly identify concentrate type at tanks, fill points, and proportioning stations.

  • Change control: require formal approvals for any concentrate refill or maintenance action.

  • Dedicated tools and procedures: prevent cross-contamination via shared hoses, totes, or transfer pumps.

  • Documentation at point-of-use: simple placards that state foam type, proportioning rate, and compatible hazards.

Where an AR-AFFF Fire Extinguisher May Fit

Portable protection can play a role in interim risk management—especially if certain liquid hazards remain credible while fixed systems are under modification. An AR-AFFF Fire Extinguisher may be specified for particular Class B scenarios where alcohol resistance is required and where your emergency planning, local codes, and internal policies allow its use.

Important: the right choice depends on the hazard, site policy, and authority having jurisdiction (AHJ) requirements. Portable equipment should support—not replace—the performance objectives of the fixed system.

FAQ: High-Intent Questions About AFFF to SFFF Conversions

Is fluorine-free foam a drop-in replacement for AFFF?

Sometimes, but often not. Many conversions require engineering validation, potential discharge device changes, and recalculated application densities to ensure the system meets performance expectations for the specific hazard.

Do we need new nozzles or sprinklers?

Possibly. Device type and foam quality can strongly affect fluorine-free performance. Some systems can be reconfigured; others require replacement or re-orificing to meet pressure and density targets.

How do we choose between SFFF and AR-SFFF?

Start with fuels. If polar solvents are credible, alcohol resistance is usually required. Your selection should be validated for the hazards and the system configuration rather than relying on general marketing claims.

What are the biggest hidden costs in a conversion?

Common surprises include cleaning and disposal logistics, water supply upgrades, discharge device changes, additional concentrate storage needs, commissioning constraints, and training time to update response tactics.

How should we handle AFFF-related waste and flush water?

Develop a controlled plan for containment, sampling, handling, and disposal that aligns with local regulations and internal environmental management standards. This is a core scope item, not an afterthought.

What tests prove the modernized system will work?

At minimum: functional tests, proportioning verification, and foam quality checks aligned to your design basis. Where feasible, scenario-based validation (or third-party witnessed testing) can add confidence for high-risk hazards.

Conversion Checklist: Next Steps for a Safe, Defensible Modernization

  • Map hazards: fuels, polar solvents, spill scenarios, and response constraints.

  • Review the legacy design basis: what the system was engineered to achieve and how it was validated.

  • Select foam based on hazard: not on convenience; validate application density and device compatibility.

  • Confirm hydraulics: water supply, pump capacity, friction loss, remote area demand.

  • Define contamination controls: cleaning vs replacement decisions and acceptable residual risk.

  • Build a disposal plan: containment, sampling, logistics, compliant disposal routes.

  • Commission in phases: water-only tests, proportioning verification, foam quality confirmation, documentation.

  • Train responders: updated application tactics and maintenance procedures.

  • Manage transition risk: segregation, labeling, change control for any areas still using AR-AFFF Foam.

If you’re planning a site-wide conversion, the most efficient path is a structured assessment that connects hazard analysis to system engineering, contamination management, and commissioning. That’s how modernization becomes not only “new foam,” but a safer and more reliable suppression program.

About Suolong
Founded in 1967, Suolong Fire, is a leading manufacturer of fire fighting foam in China, accredited to ISO9001, ISO14001, ISO45001, ISO50001. 

Quick Links

Product Category

Contact Us
   Kangmin Road, Xinghua City, Jiangsu Province, China.
 +86-13641554558(Nice Ma)
     +86-18936828180(Jesse Dai)
Leave a Message
Contact Us
Copyrights 2022  Jiangsu Suolong Fire Science and Technology Co., Ltd. Sitemap.